Sliding Rail Busway

Sliding Rail Busway

Sliding Rail Busway
Tap-off boxes reposition anywhere along the run
160–1000 A
PRODUCT DESCRIPTION

Start / Feeder Box

Integrated one-piece design connects to the trunking via connectors. Configurable with circuit breakers, SPDs, and monitoring modules; input method and operation mode set to order.

Busway Trunking

Sliding-rail aluminum-magnesium alloy enclosure, 160–1000A. Tap-off boxes lock at any point along the straight run for flexible deployment and later changes.

Plug-in (Tap-off) Box

Lightweight, high-strength aluminum-alloy enclosure with high-elasticity beryllium-copper contacts for durable, low-temperature-rise connections. Single-, three-, or six-circuit options, with anti-phase-error positioning and a quick-lock mechanism.

Connector & Bend Units

Aluminum-alloy and engineering-plastic connectors with an infrared inspection window for real-time temperature checks. L-shaped bends (standard 0.4 x 0.4m, custom 0.3–1.0m) route around obstacles without special tools.


PRODUCT SPECIFICATIONS

Sliding Rail Busway — Rated Current & Electrical Data

Rated Current (A)

100

160

200

250

315

400

630

800

1000

Dimension H x W (mm)

134.5×86.6

134.5×86.6

134.5×86.6

134.5×86.6

134.5×86.6

134.5×86.6

134.5×96.6

176.7×104.6

176.7×104.6

Weight (kg/m)

7.37

7.37

7.74

8.63

9.21

10.11

13.87

18.82

22.16

Icw Short-time (kA)

20

20

20

20

20

20

30

35

35

Ipk Peak (kA)

40

40

40

40

40

40

63

73.5

73.5

Resistance (mΩ/m)

0.318

0.318

0.257

0.182

0.158

0.122

0.084

0.0056

0.0045

Reactance (mΩ/m)

0.064

0.064

0.051

0.046

0.037

0.029

0.022

0.02

0.018

Impedance (mΩ/m)

0.347

0.347

0.281

0.206

0.172

0.134

0.095

0.059

0.047

Voltage Drop (V/m)

0.081

0.081

0.092

0.075

0.081

0.08

0.087

0.078

0.079

Standards: IEC 61439.1/6, GB 7251.1/6/8. Protection: IP54 / IP43. Insulation Voltage: 1000V / 500V. Frequency: 50/60Hz. Support Spacing: 1.5m. Tap-off Current: 16–100A.